Shaoxing Weimin Fire Fighting Equipment Co., Ltd. is one of the most reliable manufacturers and suppliers of 30 lbs powder fire extinguisher(usa module) in China. If you're going to wholesale bulk CE and ISO approved 30 lbs powder fire extinguisher(usa module), welcome to get pricelist and free sample from our factory. All customized products are with high quality and low price.
Technical Specifications
| Parameter | Value |
|---|---|
| Load Capacity | 30 lbs (13.6 kg) ABC powder |
| Working Pressure | 240 PSI |
| Test Pressure | 720 PSI (hydrostatic) |
| Cylinder Type | One-piece seamless steel |
| Temperature Range | -49°C to 54°C |
| Discharge Time | 34 seconds continuous |
| Discharge Range | 12–15 meters (40–50 ft) |
| Electrical Safety | Non-conductive up to 100,000V |
| Certification | UL 10A:160B:C / ULC dual approval |
Certification & Compliance
This extinguisher is certified under:
- UL Rating: 10A:160B:C
- ULC dual approval system
- Electrical safety classification: non-conductive up to 100,000 volts
Engineering meaning:
- 10A: solid combustible suppression performance
- 160B: liquid fire suppression capacity class
- C: safe operation in energized electrical systems
How It Works
When the valve is activated:
nitrogen gas at 240 PSI expands inside cylinder
pressure pushes 13.6 kg ABC powder through dip tube
powder exits through nozzle at 12–15 m discharge range
particles form oxygen-blocking layer on combustion surface
Physical suppression mechanisms:
oxygen displacement by particle coating
flame radical interruption in combustion zone
heat dissipation through solid particle dispersion

Cylinder Construction
- Material: one-piece seamless carbon steel cylinder
- Manufacturing: deep drawing + integrated forming process
- Pressure resistance: validated at 720 PSI hydrostatic test
Engineering function:
- eliminates weld seam stress concentration
- improves fatigue resistance under vibration and transport load
- stabilizes long-term pressure retention performance
Fire Application Scenarios
Class A Fire (Solid Combustibles)
wood pallets, paper stacks, textile storage • UL 10A classification environment • powder forms insulating surface layer
Class B Fire (Flammable Liquids)
gasoline, diesel, lubricants • UL 160B classification • powder suppresses vapor flame above liquid surface
Class C Fire (Electrical Systems)
energized equipment up to 100,000V • non-conductive discharge behavior prevents electrical conduction
Discharge Performance
- Continuous discharge time: 34 seconds
- Effective range: 12–15 meters
- Operating temperature: -49°C to 54°C
Flow behavior:
- nitrogen-driven powder acceleration
- nozzle-controlled particle dispersion
- stable discharge even under low-temperature conditions
Manufacturing & Quality Control
Production process:
seamless cylinder forming
hydrostatic test at 720 PSI
internal coating for corrosion isolation
powder filling under controlled sealing environment
valve torque-controlled assembly
nitrogen pressurization at 240 PSI
final inspection (pressure + weight + batch trace)
Each unit is assigned traceable batch ID for export inspection.
Installation & Operation
- mounting: wall bracket with M8 expansion bolts
- installation height: 0.8–1.2 m from ground
- access distance: ≤1.2 m from hazard zone
Operation sequence:
- pull safety pin
- press lever valve
- discharge begins within mechanical response time
Failure Modes & Risk Control
Potential failure points:
- valve seal leakage ➔ pressure drop below 240 PSI
- powder moisture absorption ➔ dip tube clogging
- nozzle restriction ➔ reduced discharge range
Control methods:
- hydrostatic test at 720 PSI
- sealed filling environment
- batch sampling discharge testing
Packaging & Logistics
- export carton + pallet stacking design
- vibration resistance for sea freight
- carton configuration optimized for container loading efficiency
Applications
-
industrial warehouse fire protection points
logistics storage centers
electrical equipment rooms
fuel handling zones
commercial building compliance systems
FAQ
Q1: What does UL 10A:160B:C mean?
A1: It defines fire performance for Class A solid fires, Class B liquid fires, and Class C electrical fires under UL testing standards.
Q2: Is the extinguisher safe for electrical equipment?
A2: Yes. It is non-conductive up to 100,000 volts, making it suitable for energized electrical environments.
Q3: Can the cylinder be reused?
A3: Yes. The seamless steel cylinder is refillable after inspection and pressure verification.
Q4: What is the difference between 240 PSI and 720 PSI?
A4: 240 PSI is working pressure during discharge, while 720 PSI is hydrostatic test pressure for safety validation.
Q5: What is the discharge range?
A5: The effective discharge distance is 12–15 meters depending on nozzle configuration and pressure stability.
Request for Quotation
Weimin supports industrial procurement for:
UL/ULC certified fire extinguisher distribution • Warehouse and commercial safety system integration • OEM branding and labeling customization • Container-level bulk shipment supply
We will provide: Technical specification sheet • Compliance document list • FOB quotation based on configuration
Contact Weimin Fire Fighting Equipment for RFQHot Tags: 30 lbs powder fire extinguisher(usa module), China 30 lbs powder fire extinguisher(usa module) manufacturers, suppliers, factory, 1KG ABC Powder Fire Extinguisher, 2KG ABC Fire Extinguisher, 6KG Powder Extinguisher, ABC 10LBS Fire Extinguisher, ABC Extinguisher, dry powder fire extinguishers